The 3M Graphic Film Fire-Rating Matrix
What 16 3M graphic films actually carry for fire performance — the flame-spread and smoke numbers, the substrate each specimen was mounted on, and whether the rating is a test of that product or an extrapolation from a sibling. Every row cites the 3M document it was read in.
These are 3M's published results, not our testing. Product bulletins are revised often and the reports here date from 1996 to 2023 — for a permit or a fire marshal, request the current certificate for your product and lot. Nothing here is a substitute for the authority having jurisdiction's approval. We install film; we do not certify it.
How to read a fire rating
ASTM E84 — the tunnel test — reports two numbers: a Flame Spread Index and a Smoke Developed Index. The flame spread number sets the class, and most building codes separately want smoke developed at 450 or less. 3M's own cover letters print the class boundaries:
| Class I (A) | Flame Spread Index 0-25 |
|---|---|
| Class II (B) | Flame Spread Index 26-75 |
| Class III (C) | Flame Spread Index 76-200 |
What the class alone will not tell you is what the film was mounted on when it earned that number, or whether the number belongs to that film at all. Both are recorded per row below.
The evidence behind each rating
Every row in this matrix is labelled with one of three bases. This is the distinction the category normally leaves out, and it is the one that matters when somebody official asks for paperwork.
Tested
A named third-party report tests this exact product.
Extrapolated by 3M
No test of this product. 3M supplies a signed letter attaching a sibling product's report and stating it is expected to perform comparably — a legitimate manufacturer position, but not a test of the film you are installing.
Not published
The current bulletin states no fire result and refers the question to 3M or the online catalog. Absence of a number in the document is not a failing grade — it means you must request the certificate for your lot.
What the matrix shows
A flame-spread class is a result for one specimen build, not a property of the film
Nine of the tested products here were mounted on fiber- or glass-reinforced cement board; 480Cv3 was tested on 5/8 inch Type X gypsum board instead. Same manufacturer, same test method, different backing. Because ASTM E84 measures how flame travels along a mounted assembly, the substrate is part of the result — which is why 'is this film Class A' is not fully answerable without 'mounted on what', and why a class quoted with no substrate is an incomplete answer to give a fire marshal.
'Expected comparable' is a manufacturer position, not a test
At least five products in this set — IJ180Cv3-10, IJ40C-20R, overlaminates 8518 and 8520, and 180-10 relative to 180C-10 — are covered by signed 3M letters that attach a sibling product's report and state the product is expected to perform comparably. That is a legitimate and documented basis, and for most purposes it is accepted. It is still not a test of the film in your booth, and the distinction is invisible unless you open the PDF. This matrix labels every row with which one you are getting.
A low flame-spread index does not mean the specimen did not burn
The 180C-10 report records the specimen as consumed from 0 to 8 feet with large blisters over the remainder, and the 3630 report logs blistering to 24 feet with charring to 8 feet and consumption to 6 feet — both while returning a flame spread index of 5. The index measures the rate at which flame front travels relative to red oak, not whether the material survived. Reading 'Class A' as 'will not burn' is the most common misreading of these documents.
Absence of a number in a current bulletin is normal, and it is your action item
IJ180mC, 8170 and the 3645/3647 floor overlaminates all have live bulletins that state no fire result and route the question to a 3M contact or the online catalog — in some cases while a test report for a related product sits elsewhere on 3M's own server. If your venue or AHJ wants a certificate, that request has to be made for your product and lot; it will not be satisfied by the bulletin.
Floor films are certified for slipping, not burning — do not conflate the two
3645, 3647 and 8550M carry UL 410 slip-resistance classifications with a static coefficient of friction above 0.50. UL 410 is a walkway safety standard. It says nothing about flame spread, and a floor graphic approved as slip-resistant may still need a separate flame certificate for the same installation.
US Class A and EU Class B-s1,d0 are different scales and are not interchangeable
DI-NOC is described as Class A under the US ASTM E84 and NFPA 101 framing in its technical data sheet, and as Class B-s1,d0 under EN 13501-1 in its EU declaration of performance. Both statements are correct in their own system. Quoting the European class to a US fire marshal, or the reverse, answers a question nobody asked.
Film by film — 16 products, 14 with a named test report
3M Controltac Plus 180C-10 and 180-10 · Wrap and wall vinyl
Two separate reports exist, a decade apart, on two slightly different cement-board specifications — a useful illustration that an E84 number is a result for one specimen build, not a property of the film.
| ASTM E84-00a Tested | Flame Spread 5 · Smoke Developed 5 — Class I (A) Specimen mounted on: Three 2 ft × 8 ft × 1/4 in glass-reinforced cement board sections, self-supporting [source] |
|---|---|
| ASTM E84-11a Tested | Flame Spread 10 · Smoke Developed 10 — Class I (A) Specimen mounted on: 1/4 in fiber-reinforced cement board, Grade II [source] |
Sources: 3M — Product Flammability Information, Controltac Plus 180C-10 (Omega Point Laboratories report 15300-109509, tested 17 Sep 2001) · 3M — Product Flammability Information, 180-10 White (Commercial Testing Company report 11-12111, 20 Dec 2011)
3M IJ180Cv3-10 (Controltac with Comply v3) · Wrap and wall vinyl
The single most-specified wrap film in the trade has no fire test of its own. 3M's fire document for IJ180Cv3-10 is a cover letter attaching the 180C-10 report, stating that due to similar film construction it is expected to perform comparably. If a fire marshal asks for the test on the film in your booth, this is the document that exists.
| ASTM E84 (by extrapolation) Extrapolated by 3M | Expected comparable to 180C-10: Class I (A), Smoke Developed ≤ 450 Specimen mounted on: Not tested — the attached report is 180C-10 on glass-reinforced cement board [source] |
|---|
Sources: 3M — Product Flammability Information, IJ180Cv3-10 (cover letter attaching the 180C-10 report)
3M IJ180mC Print Wrap Film · Wrap and wall vinyl
A current bulletin with no fire section to quote. This is the common case, not an oversight — request the certificate rather than assuming a class.
| Not stated in the bulletin Not published | The May 2026 bulletin gives no flame-spread or smoke result. It states that flammability standards differ by country and directs you to your local 3M contact and the fire-certificate link. Specimen mounted on: — [source] |
|---|
Sources: 3M Product Bulletin IJ180mC — Print Wrap Film (May 2026)
3M Scotchcal IJ35-10 · Wrap and wall vinyl
The most recently tested film in this set, to the current E84 revision.
| ASTM E84-23 Tested | Flame Spread 15 · Smoke Developed 10 — Class I (A) Specimen mounted on: 1/4 in fiber-cement board to ASTM C1186 Grade II, mounted per ASTM E2404 [source] |
|---|
Sources: 3M — Flammability Test Report IJ35-10 (Commercial Testing Company report 23-08020, 2 Aug 2023)
3M Envision Print Wrap Film SV480mC and LX480mC · Wrap and wall vinyl (non-PVC)
One report covers both films.
| ASTM E84-19b Tested | Flame Spread 10 · Smoke Developed 0 — Class I (A) Specimen mounted on: 1/4 in fiber-cement board to ASTM C1186 Grade II [source] |
|---|
Sources: 3M — SV480mC / LX480mC ASTM E84 report (Commercial Testing Company report 19-12102, 5 Dec 2019)
3M Envision 480Cv3 (legacy) · Wrap and wall vinyl
The substrate exception. Every other tested film in this set sits on cement board; this one was tested on Type X gypsum. Same manufacturer, same test method, different backing — which is exactly why an E84 class quoted without its substrate is an incomplete answer.
| ASTM E84-13a Tested | Flame Spread 10 · Smoke Developed 0 — Class I (A) Specimen mounted on: 5/8 in Type X gypsum board to ASTM C1396 — not cement board [source] |
|---|
Sources: 3M — Flammability Test Report 480Cv3 (Commercial Testing Company report 13-09097, 9 Sep 2013)
3M IJ40C-10R and IJ40C-20R · Wrap and wall vinyl
10R tested; 20R carries an extrapolation letter.
| ASTM E84-07 Tested | Flame Spread 15 · Smoke Developed 10 — Class I (A) Specimen mounted on: 1/4 in fiber-reinforced cement board, Grade II [source] |
|---|---|
| ASTM E84 (by extrapolation) Extrapolated by 3M | IJ40C-20R expected comparable to IJ40C-10R Specimen mounted on: Not tested [source] |
Sources: 3M — Flammability Test Report IJ40C-10R (Commercial Testing Company report 07-08140, 13 Aug 2007) · 3M — Product Flammability Information, IJ40C-20R (cover letter attaching the IJ40C-10R report)
3M Scotchcal Overlaminates 8518, 8519, 8520 · Overlaminate
Only 8519 was tested. Both 8518 and 8520 carry letters extrapolating from it. Since the overlaminate is the outermost layer facing the flame, this is the extrapolation most worth knowing about.
| ASTM E84-05 Tested | 8519: Flame Spread 15 · Smoke Developed 10 — Class I (A) Specimen mounted on: 0.003 in clear film on 1/4 in fiber-reinforced cement board, Grade II [source] |
|---|---|
| ASTM E84 (by extrapolation) Extrapolated by 3M | 8518 and 8520 expected comparable to 8519 Specimen mounted on: Not tested [source] |
Sources: 3M — Flammability Test Report 8519 overlaminate (Commercial Testing Company report 06-10313, 13 Oct 2006) · 3M — Product Flammability Information, 8520 overlaminate (cover letter attaching the 8519 report)
3M Envision Overlaminates 8548G, 8549L, 8550M · Overlaminate
The bulletin points to E84 reports for 8548G and 8550M in the online catalog rather than printing numbers; we did not obtain those reports, so no index is published here. 8550M's slip certification is a different standard entirely.
| ASTM E84 Not published | Reports referenced by the bulletin for 8548G and 8550M; no index printed in the document Specimen mounted on: — [source] |
|---|---|
| UL 410 (slip resistance) Tested | 8550M classified slip-resistant, average static coefficient of friction above 0.50 — recommended for floor graphics Specimen mounted on: Walkway surface test, not a flame test [source] |
3M Scotchcal Floor Overlaminates 3645 and 3647 · Floor graphic overlaminate
The floor-graphic trap: these carry a slip certification, not a flame one. A film 'UL classified' for floors says nothing about flame spread.
| UL 410 (slip resistance) Tested | UL Classified for slip resistance, file SA11595 Specimen mounted on: Walkway surface test, not a flame test [source] |
|---|---|
| ASTM E84 Not published | The bulletin prints no flame-spread result and refers to the online catalog or a phone call Specimen mounted on: — [source] |
Sources: 3M Product Bulletin — Scotchcal Luster Overlaminate 3645 and Matte Overlaminate 3647
3M Scotchcal Translucent 3630 · Translucent / light box
The film behind most backlit signage and light boxes.
| ASTM E84-95 Tested | Flame Spread 5 · Smoke Developed 0 — Class I (A), Smoke Developed ≤ 450 Specimen mounted on: Self-adhered to glass-reinforced cement board [source] |
|---|
3M Wrap Film 2080 · Colour-change wrap
| ASTM E84-19b Tested | Flame Spread 10 · Smoke Developed 5 — Class I (A) Specimen mounted on: 1/4 in fiber-cement board to ASTM C1186 Grade II [source] |
|---|
Sources: 3M — Product Flammability ASTM E84 Test Report, Wrap Film 2080 (report 20-02212, 20 Feb 2020)
3M DI-NOC Architectural Finishes · Architectural film
Two documents, two different classification systems, and they are not interchangeable. The EU declaration is the one with a specific class in it — and it excludes the EX- and DG-suffix products.
| ASTM E84 via NFPA 101 (US) Not published | The technical data sheet states that most products are Class A. No flame-spread or smoke index numbers and no test substrate are given; marine, fire-door and Canadian certifications are referred to 3M Technical Service. Specimen mounted on: Not stated [source] |
|---|---|
| EN 13501-1:2019-05 (EU) Tested | Reaction to fire Class B-s1,d0, tested to EN 15102 for decorative wall coverings. Covers the AE through WG series but explicitly excludes EX-suffix and DG-suffix products. Specimen mounted on: Per EN 15102 decorative wall covering mounting [source] |
Sources: 3M DI-NOC Architectural Finishes — Technical Data Sheet, Revision S (March 2024) · 3M — Declaration of Performance No. 3M DI-NOC-8, EU Regulation 305/2011 (5 March 2025)
3M FASARA Glass Finishes · Architectural glass film
One of the few 3M graphics bulletins that prints a fire classification directly in its properties table.
| DIN EN 13501 (EU) Tested | Reaction to fire Class B-s1,d0, stated in the bulletin's properties table Specimen mounted on: Per the EN classification [source] |
|---|
Sources: 3M Product Bulletin — FASARA Glass Finishes (January 2025)
3M Scotchcal ElectroCut 7125 and 7725 · Cut vinyl / lettering
3M states the class in writing; the numeric indices were not in the document we retrieved, so we publish the class and not numbers we did not read.
| ASTM E84 Tested | 3M states in writing that 7125 and 7725 meet Class I (A) with a smoke developed rating of 450 or less. Flame-spread and smoke index figures were not present in the retrieved document. Specimen mounted on: Not stated in the retrieved pages [source] |
|---|
Sources: 3M — Product Flammability Information, Scotchcal ElectroCut 7125 and 7725
3M Window Graphic Film 8170-P50 and 8170-P40 · Window / perforated
| ASTM E84 Not published | The bulletin links to E84 reports rather than printing a result; no index appears in the document. Specimen mounted on: — [source] |
|---|
Sources: 3M Product Bulletin — Window Graphic Film 8170-P50 and 8170-P40
Related references
A fire rating is only half the question — the other half is what the building you are installing in will accept. Our Venue Graphics-Rules Index covers the flame-certification, adhesive and rigging rules at 34 U.S. convention venues and the fire codes behind them. If your graphic lives outdoors in the desert, what Las Vegas heat does to film warranties covers 3M's and Avery's own desert-zone reductions.